C00352

C00353

C00354

Parameter | Name:

C00352 | CAN Slave/Master

Data type: UNSIGNED_8

Index: 24223

d

= 5E9F

h

The drive starts as CAN master after mains switching if the value "1" has been entered and saved here.

System bus "CAN on board"

Selection list

(Lenze setting printed in bold)

0 Slave
1 Master

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00353 | CAN IN/OUT COBID source

Data type: UNSIGNED_8

Index: 24222

d

= 5E9E

h

Identifier allocation procedure for the CANx In/OUT process data

System bus "CAN on board"

Selection list

Info

0 COBID = C0350 + LenzeBaseID

COBID = device address + LenzeBaseID

1 COBID = C0350 + CANBaseID

COBID = device address + CANBaseID (

C00354/x

)

2 COBID = C0354/x

COBID =

C00354/x

+ 384

Subcodes

Lenze setting

Info

C00353/1

1: COBID = C0350 + CANBaseID

COBID source CAN1_IN/OUT

C00353/2

1: COBID = C0350 + CANBaseID

COBID source CAN2_IN/OUT

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00354 | COBID

Data type: UNSIGNED_32

Index: 24221

d

= 5E9D

h

Setting of the default COBID according to CANopen

• A change of the COBID will only become effective after a CAN reset node.

System bus "CAN on board"

Setting range

(min. hex value | max. hex value)

0x00000000

0xFFFFFFFF

Value is bit-coded:

Info

Bit 0 COBID Bit0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: PDO invalid (is not transmitted)

... ...

Bit 31 PDO invalid

Subcodes

Lenze setting

Info

C00354/1

513

COBID CAN1_IN

C00354/2

385

COBID CAN1_OUT

C00354/3

769

COBID CAN2_IN

C00354/4

641

COBID CAN2_OUT

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT