C00066 | thermal motor load (i·xt), C00073 | vp imax controller, C00074 | ti imax controller – Lenze 8400 BaseLine C User Manual

Page 247: C00081 | rated motor power, C00084 | motor stator resistance, C081, C066, C084, C074/1, C074

Advertising
background image

10

Parameter reference

10.2

Parameter list | C00066

247

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00066

C00073

C00074

C00081

C00084

Parameter | Name:

C00066 | Thermal motor load (I²xt)

Data type: INTEGER_16

Index: 24509

d

= 5FBD

h

Display of the thermal motor load being detected sensorless via a motor model

• If the value displayed here exceeds the threshold set in

C00120

, the fault message "OC6: Thermal motor overload

(I2xt)" is output and the fault response set in

C00606

is executed (default setting: "Warning").

Display range

(min. value | unit | max. value)

0

%

200

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00073 | Vp Imax controller

Data type: UNSIGNED_16

Index: 24502

d

= 5FB6

h

Amplification factor Vp for Imax controller
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

16.00 0.25

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00074 | Ti Imax controller

Data type: UNSIGNED_16

Index: 24501

d

= 5FB5

h

Reset time Ti for Imax controller
Setting range

(min. value | unit | max. value)

Lenze setting

12

ms

9990 65 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00081 | Rated motor power

Data type: UNSIGNED_16

Index: 24494

d

= 5FAE

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.

Note:

It is mandatory to give the rated motor power for the sensorless vector control (

SLVC

).

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

kW

99.00 11.00 kW

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00084 | Motor stator resistance

Data type: UNSIGNED_32

Index: 24491

d

= 5FAB

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered automati-

cally. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0

mohm

200000 330 mohm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1