Important Safety Instructions

Liebert

®

CRV

2

NOTICE

Risk of overhead interference. Can cause unit and/or building damage.
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and

doorway heights and refer to the installation plans prior to moving the unit to verify

clearances.

NOTICE

Risk of improper storage, Can cause unit damage.
Keep the unit upright, indoors and protected from dampness, freezing temperatures and

contact damage.

!

WARNING

Arc flash and electric shock hazard. Can cause injury and death.
Disconnect local and remote power supplies and wear appropriate personal protective

equipment per NFPA 70E before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included

and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM

®

microprocessor does not isolate power from the unit, even in the Unit Off

mode.
Some internal components require and receive power even during the Unit Off mode of the

Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch

contains live hazardous voltage potential.
Install and open a remote disconnect switch and verify with a voltmeter that live hazardous

voltage potential is not present inside the unit cabinet before working within. Refer to the

unit electrical schematic.
Follow all national and local codes.

!

WARNING

Risk of refrigerant system rupture or explosion from overpressurization. Can cause

equipment damage, injury and death.
A pressure relief valve is required for compliance with the EU Pressure Equipment Directive

and may be required for compliance with local codes. If a discharge pressure relief device is

not provided with the condenser unit, the system installer must install one in the high side of

the refrigerant circuit and rated for a maximum of:
• 675psig (46.5bar) for water/glycol-cooled units
• 700psig (48.3bar) for air-cooled units
A shutoff valve must not be installed between the compressor and the field-installed relief

valve.
One or more additional pressure relief valves are required downstream of any and all

field-installed isolation. Do not isolate any refrigerant circuits from overpressurization

protection.

!

WARNING

Risk of top-heavy unit falling over. Can cause equipment damage, personal injury and death.
Read all of the following instructions before attempting to move, lift or remove packaging

from the Liebert CRV.

!

CAUTION

Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,

shoes and glasses should attempt to move, lift or remove packaging from the Liebert CRV or

prepare the unit for installation.