The Liebert CRV is equipped with the most advanced Liebert iCOM control system. The large Liebert

iCOM display is standard on the Liebert CRV.
Each Liebert CRV contains a return air temperature and humidity sensor, supply air temperature

sensor and three remote rack sensors. Up to an additional 7 remote rack sensors can be added to the

sensor network. Each rack sensor takes two temperature readings and reports either the average or

the maximum temperature of the two sensors.
The 2T rack temperature sensors provide feedback to the cooling unit about the condition of the air

entering the server racks. This information allows the Liebert CRV to ensure it is providing just

enough cold air to each rack, virtually eliminating hot spots. Overcooling and excessive airflow are

avoided, greatly reducing unnecessary energy consumption.
Each Liebert CRV includes three 2T rack temperature sensors to monitor three racks. A total of ten

2T temperature sensors can be connected to each cooling unit to monitor every rack a Liebert CRV is

protecting. When multiple cooling units are connected in a Unit-to-Unit iCOM control network, all

sensor data is shared to optimize their performance as a system.
2T rack sensors can also be initially installed on empty racks reserved for future growth with the

control set to ignore these sensor readings. The extra 2T temperature sensor readings can also be

displayed on the local display and reported remotely for monitoring purposes only; not impacting unit

operation. This function provides users with a built-in mini-monitoring system.
Table 22

Keyboard icons and functions

Icon

Key Name

Function

On/Off Key

Controls the operational state of the cooling unit.

Alarm Key

Silences an alarm.

Help Key

Accesses integrated Help menus.

ESCape Key

Returns to the previous display view.

Enter Key

Confirms all selections and selects icons or text.

Increase Key

(Up Arrow)

Moves upward in a menu or increases the value of a selected parameter.

Decrease Key

(Down Arrow)

Moves downward in a menu or reduces the value of a selected parameter.

Left and Right

Arrow Keys

Navigates through text and sections of the display.

Upper LED

Blinking Red—Active, unacknowledged alarm exists

Solid Red—Active, acknowledged alarm exists

Lower LED

Amber—Power is available to the unit; unit is NOT operating

Green—Unit is operating with no alarms

?