0 refrigerant connections, Efrigerant, Onnections – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 26: Notice, Warning

Advertising
background image

Refrigerant Connections

Liebert

®

CRV

18

6.0

R

EFRIGERANT

C

ONNECTIONS

NOTICE

Risk of oil contamination with water. Can cause equipment damage.
The piping must not be open to the atmosphere for extended periods because the Liebert CRV

requires POE (polyol ester) oil. POE oil absorbs water at a much faster rate when exposed to

air than previously used oils. Because water is the enemy of a reliable refrigeration system,

extreme care must be used when opening systems during installation or service. If water is

absorbed into the POE oil, it will not be easily removed and will not be removed through the

normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also

have a property that makes them act as a solvent in a refrigeration system. Maintaining

system cleanliness is extremely important because the oil will tend to bring any foreign

matter back to the compressor.

The Liebert CRV can be connected to a condenser through either the top or bottom of the unit. The

unit is piped for connections at the top of the unit as shown in Figure 14, with provision for

connection through the bottom of the unit.
Connecting through the bottom of the unit requires cutting the liquid and suction lines as shown in

Figure 15. Cutting these lines disconnects the top connections from the rest of the refrigeration system.
Air-cooled units are shipped with a holding charge of nitrogen.

!

WARNING

Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and/or gases under high pressure.
Relieve pressure before working with piping.

!

WARNING

Risk of refrigerant system rupture or explosion from overpressurization. Can cause

equipment damage, injury and death.
A pressure relief valve is required for compliance with the EU Pressure Equipment

Directive and may be required for compliance with local codes. If a discharge pressure relief

device is not provided with the condenser unit, the system installer must install one in the

high side of the refrigerant circuit and rated for a maximum of:
• 675psig (46.5bar) for water/glycol-cooled units
• 700psig (48.3bar) for air-cooled units
A shutoff valve must not be installed between the compressor and the field-installed relief

valve.
One or more additional pressure relief valves are required downstream of any and all

field-installed isolation. Do not isolate any refrigerant circuits from overpressurization

protection.

Advertising