Figure 73 Set alarms parameters screen - Page 1

Temp/Hum Events—This parameter enables or disables all of the temperature and humidity

events.
High Supply Temperature—This parameter sets the high temperature threshold that will trigger

an alarm on the Liebert iCOM

®

local display and any monitoring system that may be connected.

Low Supply Temperature—This parameter sets the low temperature threshold that will trigger an

alarm on the Liebert iCOM local display and any monitoring system that may be connected.
High Return Temperature—This parameter sets the threshold temperature when a return high

temperature alarm will occur.
High Return Humidity—This parameter sets the threshold humidity when a return high humidity

alarm will occur.
Low Return Humidity—This parameter sets the threshold humidity when a return low humidity

alarm will occur.
High CW Temperature—This parameter sets the threshold chilled water when a return high

chilled water temperature alarm will occur.

S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211

PASSWORD (Actual Level 0)

????

Tem/Hum Events

Enabled

High Supply Temperature

80 °F

Low Supply Temperature

46 °F

High Return Temperature

104 °F

High Return Humidity

60 %

Low Return Humidity

15 %

High CW Temperature

°F

SET ALARMS (page 1 of 4)