Troubleshooting

Liebert

®

CRV

114

15.0 T

ROUBLESHOOTING

Table 29

Unit diagnostics

Problem

Possible Cause

Corrective Action

Rack temperature

is too high

Dirty filters

Replace filters

Filter clog sensor failure

Call Emerson Network Power

Incorrect positioning of remote

temperature sensor(s)

Verify that remote temperature sensors are correctly

positioned

Remote temperature sensor(s) issue

Contact Emerson

Condensing pressure (head pressure) is

too high

Air-cooled units: Verify that remote condenser fan(s) are

running
Water/glycol units: Check cooling water supply
Water/glycol units: Check cooling water temp
Call Emerson Network Power

Chilled water units: inlet water

temperature is too high

Check cooling water temperature

Refrigerating circuit charge issue

Contact your local Emerson representative

Cold air short-cycling issues

Verify unit positioning/room configuration
Verify unit air baffles set-up
Verify cold aisle containment seals (if applicable)

Insufficient room-cooling capacity

Reduce rack heat load or add cooling units

(C unit) water-regulating valve issue

Contact your local Emerson representative

Unit safety devices intervention

Contact your local Emerson representative

Unit fan fails

to start

Fan is faulty

Contact your local Emerson representative

Water drops

carried by airflow

Room humidity is over acceptable limit

Check room condition

Condensate pan drain is clogged

Contact your local Emerson representative

Problem with humidifier control

Contact your local Emerson representative

Water on the floor

around the unit

Unit is not properly levelled

Adjust the levelling feet

Unit condensate drain pipe is clogged

Remove pipe obstruction

Chilled water and water/glycol units: leak

in the water circuit

Locate and repair the leak

Piping insulation broken/damaged

Restore insulation integrity

Leak in the draining circuit

Contact your local Emerson representative

Condensate pump is faulty

Contact your local Emerson representative

Leak in the humidifier filling hose

Contact your local Emerson representative

Cooling unit

noise level

is higher

than expected

Incorrect positioning of remote

temperature sensor(s)

Verify correct positioning of temperature sensors

Unbalanced heat load distribution

Redistribute rack heat load

Remote temperature sensor(s) issue

Contact your local Emerson representative

Unsteady

air delivery

temperature

Faulty temperature sensor(s)

Contact your local Emerson representative

Unit controller issue

Contact your local Emerson representative

Local display is

not operational

but unit operates

Local display cable disconnected

Connect cable

Local display cable damaged

Replace cable

Local display configuration lost

Contact your local Emerson representative

Local display is

not operational

and unit does not

operate

Unit electrical supply is Off

Restore electrical supply

Unit main switch is Off

Switch On the unit

Control board supply issue

Contact your local Emerson representative

Control board issue

Contact your local Emerson representative