Table 20 unit connections, chilled water models, Figure 25 recommended drycooler installation, Table 20 – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 44: Unit connections, chilled water models

Advertising
background image

Water Connections

Liebert

®

CRV

36

Figure 25 Recommended drycooler Installation

Table 20

Unit connections, chilled water models

Unit Connections

CR040C (50 Hz)

CR040C (60 Hz)

CWS

Chilled Water Supply

32mm GAS F

1-1/4" FPT

CWR

Chilled Water Return

32mm GAS F

1-1/4" FPT

GD

Gravity Coil Pan Drain

20mm I.D.

1" MPT

GDH

Gravity Humidifier Drain

22mm I.D.

N/A

HS

Humidifier Supply

1/2" GAS F (top connection)

3/4" GAS F (bottom connection)

1/2" FPT (top connection)

1/4" Compression Fitting

(bottom connection)

CP

Condensate Pump

1/2" GAS F

1/2" FPT

HVT

High Voltage Top Connection

Combination Knockout Hole

Diameter 1-3/8" (35mm)

1-3/4" (44.5mm) and 2-1/2" (63.5mm)

Combination Knockout Hole

Diameter 1-3/8" (35mm)

1-3/4" (44.5mm) and 2-1/2" (63.5mm)

HVB

High Voltage Bottom Entrance

(feed through the base of the unit)

Hole Diameter

2-1/2" (63.5mm)

Knockout Hole Diameter

2-1/2" (63.5mm)

LVT

Low Voltage Top Connection

Hole Diameter

7/8" (22mm) 2 places

Knockout Hole Diameter

7/8" (22mm) 4 Places

LVB

Low Voltage Bottom Entrance

(feed through the base of the unit)

Hole Diameter

1-7/64" (28mm) 2 places

Knockout Hole Diameter

1-3/32" (27.8mm) 2 Places

LVB2

Low Voltage Bottom Entrance

(feed through the base of the unit)

Combination Knockout Hole

Diameter 1-3/4" (44.5mm) 1 Place

Source: DPN001794, Rev. 2

APPLIANCE

TS

HTC

Filling

Water

(optional)

HTC

TS

Shutoff Valve
Pump

Check Valve

Gauge

Thermostat
Variex (50Hz Opt.)

Safety Valve

Expansion Tank

Air Separator

Charge Group (Filter,
Reducer, Check Valve)

Filling Meter
Drain (at Lowest Point)

(*)

Standby Pump

Standby Pump

Pre

ss

ure

-O

pe

ra

te

d B

yp

as

s

See hydraulic drawings in the Appendix D

Disconnect
After Charge

Advertising