Important Safety Instructions

3

Liebert

®

CRV

NOTICE

Risk of water leakage. Can cause severe property damage and loss of critical data center

equipment.
This unit requires a water drain connection. It may require an external water supply to

operate the humidifier. Improper installation, application and service practices can result in

water leakage from the unit.
Do not locate the Liebert CRV directly above any equipment that could sustain water damage.

Emerson recommends installing monitored leak detection equipment for the unit and supply

lines.

NOTICE

Risk of frozen fluids. Can cause equipment damage and building damage.
Freezing system fluids can rupture piping. Complete system drain-down cannot be ensured.

When the field piping or unit may be exposed to freezing temperatures, charge the system

with the proper percentage of glycol and water for the coldest design ambient.
Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system.

NOTICE

Risk of corrosion. Can cause equipment damage.
Read and follow individual unit installation instructions for precautions regarding fluid

system design, material selection and use of field-provided devices. Liebert systems contain

iron and copper alloys that require appropriate corrosion protection.
Contact a local water consultant regarding water quality, corrosion and freeze protection

requirements.
Water chemistry varies greatly by location, as do the required additives, called inhibitors,

that reduce the corrosive effect of the fluids on the piping systems and components. The

chemistry of the water used must be considered, because water from some sources may

contain corrosive elements that reduce the effectiveness of the inhibited formulation.

Sediment deposits prevent the formation of a protective oxide layer on the inside of the

coolant system components and piping. The water/coolant fluid must be treated and

circulating through the system continuously to prevent the buildup of sediment deposits and

or growth of sulfate reducing bacteria.
Preferably, surface waters that are classified as soft and are low in chloride and sulfate ion

content should be employed. Proper inhibitor maintenance must be performed in order to

prevent corrosion of the system. Consult glycol manufacturer for testing and maintenance of

inhibitors.
Commercial ethylene glycol (Union Carbide Ucartherm, Dow Chemical Dowtherm SR-1 and

Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive to the common

metals of construction than water itself. It will, however, assume the corrosivity of the water

from which it is prepared and may become increasingly corrosive with use if not properly

inhibited.

NOTICE

Risk of no-flow condition. Can cause equipment damage.
Do not leave the unit in a no-flow condition. Idle fluid allows the collection of sediment that

prevents the formation of a protective oxide layer on the inside of tubes. Keep unit switched

On and system pump operating.

NOTE
The Liebert indoor cooling unit has a factory-installed high pressure safety switch in the high

side refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp

condensers.

Consult your local building code to determine if the Liebert VFD condensers will require

field-provided pressure-relief devices. A fusible plug kit for Liebert VFD condensers is available

for field installation.