When the Liebert iCOM

®

calls, the cylinder fills to 100% of the Full Load Amperage (FLA) or to the

top of the cylinder, whichever comes first. See Figure 100. If it reaches 100% FLA, the water heats

and boils away to a level giving 80% FLA. An electronic timer uses the rate of amp fall to determine

the water level. The objective is to concentrate current carrying minerals in the cylinder so that a

smaller volume of water is required to produce the rated steam output. This extends the life of the

disposable cylinder by minimizing electrode coverage and reducing energy use because the high

concentration allows a minimal drain rate. When 80% FLA is reached, the fill valve will open,

refilling the cylinder to 100% FLA. On occasion, the drain valve will also come on if the water level is

too low, indicating too high a concentration and the need to dilute the water in the cylinder. If the

water reaches the top of the cylinder before 100% FLA, the fill valve shuts Off via the sensor, and the

fill-boil-fill-boil cycle continues, cycling Off the red high water sensor light until the concentration

becomes high enough to reach 100% FLA. The above-described control process will then take over.

Figure 100 General diagram—humidifier operation

NOTE
The Liebert iCOM control monitors the condition of the air discharging from the unit to protect

neighboring electronic equipment. The Liebert iCOM will prevent the humidifier from

activating if the discharge air is near its saturation point. This protects against discharging

fog from the unit or condensation forming on the unit’s supply air baffles. This protection mode

is activated when the supply air leaving the unit is below 64°F (17.8°C) or above 55% relative

humidity. The Liebert iCOM screen will display “Humidifier Suspended.” The screen will

display “Humidifier Resumed” when the protection mode resets at 67°F (19.4°C).