Electrical Connections

37

Liebert

®

CRV

8.0

E

LECTRICAL

C

ONNECTIONS

8.1

Electrical connections

Figure 26 Remove electrical panel and lower front panel

!

WARNING

Arc flash and electric shock hazard. Can cause injury and death.
Disconnect local and remote power supplies and wear appropriate personal protective

equipment per NFPA 70E before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included

and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM

®

microprocessor does not isolate power from the unit, even in the Unit Off

mode.
Some internal components require and receive power even during the Unit Off mode of the

Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch

contains live hazardous voltage potential.
Install and open a remote disconnect switch and verify with a voltmeter that live hazardous

voltage potential is not present inside the unit cabinet before working within. Refer to the

unit electrical schematic.
Follow all national and local codes.

!

WARNING

Risk of electric shock. Can cause injury or death.
This unit has a high leakage current potential. Proper earth ground connection per national

and local codes is required before connection to the electric power supply.

Remove these bolts

to access low voltage

electrical panel

Remove these bolts

to access high voltage

electrical panel

Remove these bolts to open

lower front baffle panel