3 entering a password, Figure 43 entering a password – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 61

Advertising
background image

Liebert iCOM

®

Control

53

Liebert

®

CRV

change the unit being viewed. Pressing the ESC key will go back a level. Figures 44 and 45 show the

Liebert iCOM

®

control menus for a stand-alone large display and for a networked large display,

respectively.

10.1.3 Entering a Password

To change the value of a parameter in a menu, you must first enter the password for that menu. Each

menu—User, Service and Advanced—has a unique password to prevent unauthorized changes.

The User menu password is 1490; the Service menu password is 5010.

To enter a password:
1. Navigate to the menu that contains the parameter to be changed.
2. Select Password in the submenu by pressing the Enter key
3. Press the Enter key to move your cursor to the right side of the screen to select the question

marks.

4. Use the arrow keys to enter the numeral for the password’s first digit (the up arrow key moves

from 1 to the next digit).

5. Use the right arrow key to move to the next question mark and repeat Step 4 to enter all digits in

the password.

6. After entering the password, press enter.
If the password is correct, the Actual Level shown to the right of Password will change

from 0 to 1 or 2. The menu will remain locked if the password was incorrect.

Figure 43 Entering a password

NOTE
Settings are readable without a password, but changing settings requires a password.

NOTE
Entering the Service menu password permits access to both the User and Service menus;

changes can then be made to parameters in either level.

NOTE
Returning to the Status menu will require re-entering a password to make changes.

SETPOINTS

to change parameter

to confirm

to select parameter

for next/previous unit
then

PASSWORD (Actual Level 0)

Temperature Setpoint
Humidity Setpoint
Humidity Control Type
Supply Sensor
Supply Setpoint
Backup Temperature Setpoint

????

73°F

50.0%

Relative

Control

50°F
73°F

UNIT 01

U101
U102
U103
U104
U105
U106
U107
U108
U109
U110
U111