Operation in Teamwork Mode

99

Liebert

®

CRV

Wall-Mount Large Display

The Liebert CRV has a large display as standard equipment. Only large displays can be used for

remotely monitoring and controlling cooling units connected on the same network. Each wall-mount

large display requires 120V input power; Liebert provides an AC adapter wall plug. A straight-

through Ethernet cable must be connected between the network switch and the P64 port on the back

of the display. This will enable control and monitoring capabilities to any cooling unit connected to the

network.

Figure 92 Wiring a large display for U2U network operation

11.4 Teamwork Modes

Groups of cooling units connected to a network can be set up to work together in any of three

teamwork modes:

• No Teamwork
• Teamwork Mode 1
• Teamwork Mode 2

All Liebert iCOM-controlled cooling units on a network must be set to run in the same teamwork

mode.

Liebert iCOM
I/O Board

Straight-Through
Ethernet Cables

CAN
Cable

See Note 4

Large Graphics Display

(Rear View)

To / From Other
Networked Units

U2U Networking Switch
(Field-Supplied)