Figure 58 Setpoints parameters screen - Page 2

Humidity Setpoint—This parameter allows the user to select a humidity that the cooling unit will

maintain by removing or adding moisture to the air. This parameter is adjustable from 20-80%. The

factory default setting from the factory is 50%.
Humidity Control Type—This parameter selects the humidity control calculation. Setting this

parameter to “Relative” will control the humidity without considering any temperature deviations.

“Predictive” and “Absolute” control consider the temperature deviation from temperature setpoint so

that a constant level of moisture is kept in the area based on the humidity sensor reading and the

temperature deviation from setpoint. The factory default setting is “Predictive.”
Humidity Deadband—This parameter can be set to avoid overshooting of the setpoint and cycling

between humidification and dehumidification. The value entered into this field will be split in half by

the temperature setpoint. Example: If the humidity setpoint is 50% and a 4% deadband is set then no

humidity control will be activated between 48% and 52%.
Humidity Proportional Band—This parameter adjusts the activation points of the humidifier and

compressors based on the actual sensor values deviation from setpoint. The smaller this number the

faster the compressors and humidifier will increase capacity, too small of a number may cause the

unit to short cycle or overshoot setpoint.
Humidity Integration Time—This parameter adjusts the capacity of the unit based on time away

from setpoint so that accurate humidity control can be maintained. This parameter is only active

when Control Type is set to “PI.”
Dehum Proportional Band—The parameter adjusts the activation points of dehumidification

based on the actual sensor values deviation from setpoint. The smaller this number the faster the

compressors and humidifier will increase capacity, too small of a number may cause the unit to short

cycle or overshoot setpoint.
Dehum Integration Time—This parameter adjusts the capacity of the unit based on time away

from setpoint so that accurate humidity control can be maintained. This parameter is only active

when control type is set to “PI”.
Dehum/Heat Low Limit 1—This parameter sets the temperature at which the compressor will be

deactivated for dehumidification control. Example—If Low Limit 1 is set to 4°F (2.2°C) and the

temperature setpoint is 70°F (21.1°C), then dehumidification will turn off at 66°F (18.8°C).
Low Limit 1 reset—This parameter controls when the temperature has increased enough to re-

enable dehumidification.

S112
S113
S114
S115
S116
S117
S118
S119
S120
S121
S122

PASSWORD (Actual Level 0)

????

Humidity Setpoint

45%

Humidity Control Type

PI

Humidity DeadBand

5%

Humidity Proportional Band

5%

Humidity Integration Time

0min

Dehum Proportional Band

5%

Dehum Integration Time

0min

Dehum/Heat Low Limit 1

-9°F

Low Limit 1 reset

0°F

SETPOINTS (page 2 of 4)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then