Figure 33 Figure 2T rack sensor

9.5.1 DIP Switch Settings

Three 2T sensor housings are included with each Liebert CRV. The DIP switches in these sensors

have been preset at the factory. It is recommended that you confirm that the DIP switches have been

set correctly using the below table. Any additional 2T sensor housings will need their dip switches set

per the below table. If the dip switches are not set correctly, the control will not operate properly.

Figure 34 DIP switches in 2T sensors

Table 21

DIP switch settings

2T Rack Sensor

DIP Switch Position

Factory-Set

to Terminated

1

2

3

4

5

6

7

8

Included with Liebert CRV
Sensor # 1

Off

Off

ON

Off

ON

off

off

off

Sensor # 2

ON

Off

ON

Off

Sensor # 3

Off

ON

ON

Off

Yes

Optional 2T Rack Sensors
Sensor # 4

ON

ON

ON

Off

ON

off

off

off

Sensor # 5

Off

Off

Off

ON

Sensor # 6

ON

Off

Off

ON

Sensor # 7

Off

ON

Off

ON

Sensor # 8

On

ON

Off

ON

Sensor # 9

Off

Off

ON

ON

Sensor # 10

ON

Off

ON

ON

Each temperature
probe wire is 1830mm
(6 feet) long

Temperature sensing probe

2T Sensor

Back

Front View

Source DPN001983 rev0

86

(3-3/8")

41

(1-

5

/8

")

4.5

(3/16"

)

67 (2-5

/8

")

Max. depth

41 (1-5/8")

112 (

4-7/1

6")

Switch Up = ON

Switch Down = OFF