Table 25 controlling sensor settings, 4 event log, 5 spare part list – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 70: 6 wellness—next maintenance calculation, 1 calculation of next maintenance and diagnostics, Event log, Spare part list, Wellness—next maintenance calculation, Table 25, Controlling sensor settings

Advertising
background image

Liebert iCOM

®

Control

Liebert

®

CRV

62

The supply temperature Setpoint may require adjusting since it will be dependent on the distance of

the CRV to the server racks being cooled. This temperature will also be dependant on rack blanking

panels, server population and if containment is being used

.

Table 25 shows the flexibility of the Liebert CRV and how the different sensor configurations can be

used to control the Liebert CRV fan speed and cooling capacity. The table shows the different coupled

and decoupled modes available for the Liebert CRV.

10.4 Event Log

The event log displays all events and actions that have been generated by the unit. When multiple

units are networked you will see the event log of the whole system. Each event shows the unit that

generated the alarm, time and date stamp, a description and the event type.

10.5 Spare Part List

The spare parts lists contains a detailed description and part number that can be used to order parts

for the unit. These part numbers are specific to each model and option installed on the unit.

10.6 Wellness—Next Maintenance Calculation

The next maintenance calculation, as well as the included diagnostics feature, will help keep the

cooling unit running at peak performance to ensure minimum component stress and maximum

reliability. The diagnostics will help the service engineer evaluate the unit’s operation since the last

maintenance.

10.6.1 Calculation of Next Maintenance and Diagnostics

If the unit includes any of the following components, they are included in the calculation:

• Fan(s)
• Compressor 1
• Compressor 2
• Electric Heaters
• Humidifier

For each component, the next maintenance will be calculated from the following parameters:

• Standard service interval (1, 2 or 4 times a year) (to be set)
• Working hours (counted)
• Number of starts (counted)
• Average running time (calculated)
• Optimum number of starts per hour (to be set)
• Maximum number of starts per hour (to be set)
• Maximum bonus to enlarge time to next maintenance (to be set)
• Maximum penalty to reduce time to next maintenance (to be set)

Table 25

Controlling sensor settings

Cooling Control

S103Cool / S125 Fan

Supply

Remote Sensor

Return

Fan Control

Supply

Factory Default

(Coupled)

N/A

N/A

Remote Sensor

Recommended

(Decoupled)

X

(Coupled)

N/A

Return

X

(Decoupled)

X

(Decoupled)

X

(Coupled)