Remove the Old Cylinder

1. Turn Off the water supply to the unit.
2. The old cylinder must be drained completely before removing. This is done by pushing the auto

On/Off/Drain switch to the “drain” position.

3. When the cylinder is empty, push the auto On/Off/Drain switch to the Off position.
4. Open the main disconnect switch during the entire cylinder change operation.
5. The power wires to the cylinder are attached by cylinder plugs to the electrode pins on top of the

cylinder. Pull these plugs off the pins.

6. Using a slotted screwdriver, loosen the steam hose clamp(s) and pull the steam hose off.

The cylinder is now ready to be lifted out of the unit.

Installing the New Cylinder

1. Leave the main disconnect open until the cylinder is completely installed and reconnected.
2. Ensure that the cylinder mounting stubs are seated properly in the allotted side mounting slots

within the unit.

3. The white sensor plug on all units is for the sensor pin, which always goes on the single pin offset

from the others.

4. Ensure that cylinder plugs are snug on the pins.
5. Replace loose-fitting plugs; loose plugs may generate enough heat to melt and destroy the plug,

and new cylinder plugs must be ordered.

Reverse the procedure to install a new cylinder.

Figure 102 Sensor pins, cylinder plugs

Humidifier Maintenance

Extended Shutdown

Always drain the cylinder before disconnecting power to the humidifier for a period of extended

shutdown. Otherwise, the electrodes are subject to harmful corrosion, which drastically shortens the

cylinder life. Do not leave the switch in the DRAIN position indefinitely because the drain coil could

burn out. Leave the switch in the Off position and open the main external fused disconnect to stop

power to the humidifier. Close the shutoff valve in the water supply line feeding the humidifier.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within. The plumbing

and electrical compartments contain high-voltage components and wiring. The access cover is

attached with screws. Access should be limited to authorized personnel only.

Cylinder Pin

Cylinder Pin

Sensor Pin

Cylinder
Plug

White
Sensor
Plug