Humidifier Fill—This activates just the humidifier water source solenoid valve which fills the

humidifier pan or canister with water.
Humidifier—This activates the humidifier system in its entirety.
Humidifier Drain—This activates just the humidifier drain solenoid in the case of the steam

generating humidifier, allowing water to drain from the canister.
Humidifier Current—In the case of the steam generating humidifier option this setting shows the

amount of AC amperes the system is consuming.

Figure 70 Diagnostics / service mode parameters screen - Page 4

Alarm Relay—This allows the user to activate the Liebert iCOM

®

control’s common alarm relay

output.
Warning Relay—This allows the user to activate the Liebert iCOM control’s free-cooling relay

output.
3P Actuator Open—This setting will energize the open circuit of the 3P type chilled or freecooling

control valve thus journeying it to the open state.
3P Actuator Close—This setting will energize the close circuit of the 3P type chilled or freecooling

control valve thus journeying it to the closed state.
Current Fanspeed (Read only)—Shows the analog output for the fan in automatic mode.
Fanspeed Manual Setpoint (Read only)—Drives the analog output for the fan in manual mode.
Condenser Control Mode—Defines the condenser control mode in manual or auto mode during

compressor manual mode.
Current MBV / CWV (AnaOut2) (Read only)—Shows the analog output for the MBV (motorized

ball valve) or analog CWV (chilled water valve) in automatic mode.
Manual MBV (AnaOut2)—Drives the analog output for the condenser valve (MBV) in manual

mode.
Manual CWV (AnaOut2)—Drives the analog output for the analog CWV (chilled water valve) in

manual mode.

to change parameter

for next/previous unit

to select parameter

to confirm

then

S334
S335
S336
S337
S338
S339
S340
S341
S342
S343
S344

PASSWORD (Actual Level 0)

????

Alarm Relay

Off

Warning Relay

Off

3P Actuator Open

Off

3P Acuator Close

Off

Current Fanspeed
Fanspeed Manual Setpoint
Condenser Control Mode

Auto

Current MBV/CWV (AnaOut 2)

75%

Manual MBV (AnaOut2)

100%

Manual CWV (AnaOut2)

%

DIAGNOSTICS/SERVICE MODE (page 4 of 6)

UNIT 01