Table 11 unit connections, air-cooled models, Table 11, Unit connections, air-cooled models – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 33

Advertising
background image

Refrigerant Connections

25

Liebert

®

CRV

Table 11

Unit connections, air-cooled models

Unit Connections

CR20A (50Hz)

CR35A (50Hz)

CR20A (60Hz)

CR35A (60Hz)

RL

Refrigerant Liquid

Line Inlet

12mm O.D. Cu Sweat 16mm O.D. Cu Sweat

1/2" O.D. Cu Sweat

5/8" O.D. Cu Sweat

RG

Refrigerant Gas

Line Outlet

16mm O.D. Cu Sweat 22mm O.D. Cu Sweat

5/8" O.D. Cu Sweat

7/8" O.D. Cu Sweat

GD

Gravity Coil Pan Drain

20mm I.D.

1" MPT

GDH Gravity Humidifier Drain

22mm I.D.

N/A

CP

Condensate Pump

1/2" GAS F

1/2" FPT

HS

Humidifier Supply

1/2" GAS F (top connection)

3/4" GAS F (bottom connection)

1/2" FPT (top connection)

1/4" Compression Fitting (bottom connection)

HVT

High Voltage

Top Connection

Combination Knockout

Hole Diameter 1-3/8" (35mm)

1-3/4" (44.5mm) and 2-1/2" (63.5mm)

Combination Knockout Hole

Diameter 1-3/8" (35mm)

1-3/4" (44.5mm) and 2-1/2" (63.5mm)

HVB

High Voltage Bottom

Entrance (feed through

the base of the unit)

Hole Diameter 2-1/2" (63.5mm)

Knockout Hole Diameter 2-1/2" (63.5mm)

LVT

Low Voltage

Top Connection

Hole Diameter 7/8" (22mm) 2 places

Knockout Hole Diameter 7/8" (22mm)

2 places

LVB

Low Voltage Bottom

Entrance (feed through

the base of the unit)

Hole Diameter 1-7/64" (28mm) 2 places

Knockout Hole Diameter 1-3/32" (27.8mm)

2 places

LVB

2

Low Voltage Bottom

Entrance (feed through

the base of the unit)

Knockout Hole Diameter 1-3/4" (44.5mm)

1 place

Source: DPN001792, Rev.2

Advertising