6 remote rack sensor operation and rack view setup, Remote rack sensor operation and rack view setup – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 57

Advertising
background image

Startup

49

Liebert

®

CRV

Located in the Service / Rack Setup Menu of the Liebert iCOM

®

display, the sensors can be set up to

either display or control temperature, give them a rack name and draw a rack layout that can be

viewed in the User menu.

9.5.6 Remote Rack Sensor Operation and Rack View Setup

Figure 38 Rack setup screen, page 1 of 3

Once the remote rack sensors have been configured and plugged into the CAN bus network, the

control can be configured to use the sensor for either control or reference. If the sensor is set to

“Disable,” it will be ignored. The sensor node number corresponds to the DIP switch assignment of the

sensor.

Figure 39 Rack setup screen, page 2 of 3

Once a sensor has been assigned to either control or display its temperature data a virtual position

can then be assigned to the sensor. This screen configures the Rack View layout in the User menu.

This step is not required for the sensor to operate but does provide a logical position in the row for

quickly referencing affected racks near the Liebert CRV. To set up navigate using the arrow and enter

keys to highlight the Assign Sensors number range. Once the range is selected then press the enter

key to move to the rack location blocks at the bottom of the screen. The Up and Down arrow keys can

be used to select the sensor node number. For the Liebert CRV select “CRV.”

Rack Setup (page 1 of 3)

UNIT 01

S901

PASSWORD (act. Level 0)

????

S902

Remote Sensor Node 01

Control

S903

Remote Sensor Node 02

Reference

S904

Remote Sensor Node 03

Disable

S905

Remote Sensor Node 04

Control

S906

Remote Sensor Node 05

Reference

S907

Remote Sensor Node 06

Disable

S908

Remote Sensor Node 07

Control

S909

Remote Sensor Node 08

Reference

S910

Remote Sensor Node 09

Disable

S911

Remote Sensor Node 10

Control

pr e s s: f or ne x t / pr e v unit ; a nd t o s e l e c t pa r a me t e r
pr e s s: , t he n t o c ha nge pa r a m e t e r

Rack Setup (page 2 of 3)

Liebert CRV

= CRV

No Sensors

= NoS

No rack

= [blank]

Sensor Note

= 01-10

Assign Names : 01-06

07-12
13-18
19-22

02

00

00

00

00

00

01

03

04

05

06

DC01

DC03

DD02

DC05

DC07

DD04 CRV

DC09

DC11

00

00

00

00

08

07

00

CRV

00

00

00

Cold Aisle

Use the navigation keys to move from rack to rack,
Enter to select a rack, and up- or down keys to
scroll through options.

UNIT 01

Advertising