Liebert iCOM

®

Control

Liebert

®

CRV

84

Figure 74 Set alarms parameters screen - Page 2

Customer Input 1, 2, 3 & 4—These parameters select the device and operation of the customer

inputs. Each event reflects a different alarm and possible action to the unit. Refer to table 7 for a

description of selectable options.
Customer Input 1, 2, 3 & 4 active when—These parameters select whether the input is a normally

closed or normally closed input.

Figure 75 Set alarms parameters screen - Page 3

This screen selects the operation of an active alarm. Each event can be enabled or disabled and can be

set to operate as an alarm, warning or message. The delay is the time the control waits before

reporting the event.

• Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes

the red LED on the display

• Warning / Alarm: Annunciates the buzzer, triggers a monitoring event, shows the event in the

event viewer / front display and flashes the red LED on the display.

• Message: Shows the event in the event viewer and on the front display.

S211
S212
S213
S214
S215
S216
S217
S218
S219
S220
S221

PASSWORD (Actual Level 0)

????

Customer Input 1

Smoke Alarm

Customer Input 1 active when

Closed

Customer Input 2

Fire Alarm

Customer Input 2 active when

Closed

Customer Input 3

C PMP Alarm SD

Customer Input 3 active when

Closed

Customer Input 4

HUM

Customer Input 4 active when

Closed

SET ALARMS (page 2 of 4)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then

S223
S224
S225
S226
S227
S228
S229
S230
S231
S232
S233

PASSWORD (Actual Level 0)

????

DELAY

EN-DIS

TYPE

LOSS OF POWER

ENABLE WRN

SMOKE DETECTED

5

ENABLE ALM

WATER UNDER FLOOR

5

ENABLE ALM

LOSS OF FLOW

5

ENABLE ALM

CUSTOMER INPUT 1

5

ENABLE ALM

REHEAT LOCKOUT

5

ENABLE ALM

HUMIDIFIER LOCKOUT

5

ENABLE ALM

COMPRESSOR(S) LOCKOUT

5

ENABLE ALM

SET ALARMS (page 3 of 4)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then