Water Connections

29

Liebert

®

CRV

7.0

W

ATER

C

ONNECTIONS

7.1

Water Connections—Supply Humidifier and Drain Water, All Models

Units with a condensate pump and humidifier are preset to be connected from the top. If floor

connections are used, the water lines can be intercepted at the following points:

Figure 19 Water connection points, bottom entry

• Condensate drain without pump:

• Use tubing rated to carry water up to 212°F (100°C) copper, PVC or flexible polythene tubing.
• Allow a 2% gradient toward the drain.
• Drain is trapped internally. Do not trap the drain external to the equipment.
• Fill the drain trap with water.

• Humidifier (optional): See Appendix A - Humidifier.

Table 16

Water connection options

Liebert CRV Option

Top Connections

Bottom Connections

Condensate Pump

and Humidifier

Available

Available

Condensate Pump

and No Humidifier

Available

Available

No Condensate Pump

and No Humidifier

Not Available

Available

Table 17

Volume of CRV internal water circuits

Model

Volume

CR020RW

4.8 liters, 1.27 gallons

CR035RW

5.7 liters, 1.51 gallons

CR040RC

17.6 liters, 4.65 gallons

Condensate

Pump Drain

Humidifier Water Supply