Humidifier

Liebert

®

CRV

122

Table 31

Humidifier troubleshooting

Unit Status Lamp

Symptom Corrective

actions

Yellow Green

On

On

Maximum water level inside

cylinder.

This usually happens on initial start-up after replacing the

cylinder (normal). Water is concentrated with minerals

inside the cylinder. Let unit run; yellow light will disappear

when the unit is at full output. This may take a day or two.

Off

Off

No power to the board.

Check for main power supply fault. Turn power switch to

'Drain' position. If drain valve is activated (sound of

solenoid), check connection to the board or board itself.

When no sound is present, check fuse (replace with 3.0 A if

needed), transformer (voltage should be present between

fuse holder and ground screw).

1 flash

sequence

Off

Excess current. Operating

amperage exceeded 130% of rated

amps. Water is drained from the

cylinder (drain valve on for 10

minutes).

Check drain valve operation, drain time, possible drain

restrictions. Check fill valve for leaks (not holding supply

water). Back pressure may also cause very conductive

water conditions. Was the humidifier short cycling? Check

for short cycling. Water conductivity too high.

2 flashes in

sequence

Off

No current detection for 30 minutes

with continuous call for humidity.

Check water level in the cylinder - should be more than 1/4

full. If not, check fill rate, 24 VAC voltage on fill valve

terminals (unit must be on with call for humidity - green light

on steadily). Verify fresh water supply to the humidifier.

Leaking drain valve may be at fault (minerals blocking the

plunger). If cylinder is more than 1/4 full, check primary

power, connections to the cylinder, continuity of wires to

cylinder. Are power wires connected to proper terminals on

the cylinder? (Color coding.) Possibly wrong cylinder type.

Low water conductivity.

4 flashes in

sequence

Off

End of cylinder life - change

cylinder.

Check water level in the cylinder; should be about 3/4 full.

Check for foaming if water level is lower or cylinder life

shorter than expected. Change cylinder, clean drain valve.