0 maintenance, 1 safety instructions, Aintenance – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 115: Safety instructions, Notice, Warning

Advertising
background image

Maintenance

107

Liebert

®

CRV

14.0 M

AINTENANCE

14.1 Safety Instructions

All maintenance operations must strictly observe national, state and local accident prevention

regulations, especially the regulations concerning electrical systems, refrigerators and manufacturing

resources.
Air conditioning equipment maintenance may be performed only by authorized properly trained and

qualified personnel.
To keep all warranties valid, the maintenance must adhere to the manufacturer’s regulations.

NOTICE

Risk of improper maintenance. Can cause equipment damage.
All maintenance must be performed only by authorized properly trained and qualified

personnel.

Ignoring safety instructions can be dangerous to persons as well as to the environment. Soiled parts

always cause a loss of performance and, for switch or control devices, can lead to the breakdown of a

plant.

!

WARNING

Arc flash and electric shock hazard. Can cause injury and death.
Disconnect local and remote power supplies and wear appropriate personal protective

equipment per NFPA 70E before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included

and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM

®

microprocessor does not isolate power from the unit, even in the Unit Off

mode.
Some internal components require and receive power even during the Unit Off mode of the

Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch

contains live hazardous voltage potential.
Install and open a remote disconnect switch and verify with a voltmeter that live hazardous

voltage potential is not present inside the unit cabinet before working within. Refer to the

unit electrical schematic.
Follow all national and local codes.

!

WARNING

Risk of contact with rotating fan blades and extremely hot and/or cold surfaces. Can cause

equipment damage, injury and death.
Disconnect all local and remote electric power supplies before working within. Perform

maintenance only when the system is de-energized, all fan blades have stopped rotating and

component temperatures have become safe for human contact.
• Turn Off the system by switching it Off at the controller and the main disconnect switch.
• Post a warning sign saying “Do not switch on.”
• Electrical components of the unit must be switched Off and checked using a voltmeter to

ensure they are not receiving electrical input power.

!

WARNING

Risk of hair, clothing and jewelry entanglement with high speed rotating fan blades. Can

cause equipment damage, serious injury or death.
Keep hair, jewelry and loose clothing secured and away from rotating fan blades during

operation.

Advertising