12.1 Alarms/Events

The following alarms and events are supported by the Liebert iCOM

®

control on the Liebert CRV.

When an alarm is triggered the alarm sounds, the LED will flash red, an event will be written to the

Event Log and the BMS will be notified. If the alarm is acknowledged, the alarm will silence and the

LED will turn solid red. When the alarm condition is resolved, the LED lights green and the BMS

alarm notification is reset.

General Alarm

Unit 07 Disconnected

Dig Scroll1 High Temp

Unit 31 Disconnected

Comp 1 High Pressure

Unit 08 Disconnected

Smoke Detected

Unit 32 Disconnected

Comp 1 Low Pressure

Unit 09 Disconnected

Water Under Floor

System Off Requested

High CW Temp

Unit 10 Disconnected

Cond Pump-High Water

System Off Confirmed

Loss of CW Flow

Unit 11 Disconnected

Loss of Flow

Fire Alarm

Loss of Airflow

Unit 12 Disconnected

El Heat1 Hrs Exceeded

Heaters Overheated

Clogged Filters

Unit 13 Disconnected

Unit Code Missing

Condenser 1 Failure

Customer Input 1

Unit 14 Disconnected

Loss of Power

Humidifier Cylinder Worn

Customer Input 2

Unit 15 Disconnected

Reheat Lockout

Maintenance Done

Customer Input 3

Unit 16 Disconnected

Heat Rej VFD

Maintenance to be Done!

Customer Input 4

Dscroll 1 Sensor Fail

Humidifier Lockout

Top Fan Failure

LP Transducer 1 Fail

On-Off Key Disabled

Heat Rej TVSS

Control Valve Failure

Call Service

Lwd Sensor Fail

Compressor(S) Lockout

Fluid Sensor Failure

High Temperature

Hum Disabled

Humidifier Low Amps

High Supply Temperature

Unit Hrs Exceeded

Hum Enabled

Comp 1 Short Cycle

Low Supply Temperature

Comp 1 Hrs Exceeded

RAM / Battery Fail

Humidifier High Amps

High Return Humidity

Hum Hrs Exceeded

Low Memory 1

Humidifier Low Water

Low Return Humidity

Supply Sensor Failure

No Connection w/Unit1

Unit 17 Disconnected

Rack Sensor 1 Failure

Room Sensor Failure

Hp Transducer 1 Fail

Unit 18 Disconnected

Rack Sensor 2 Failure

Network Failure

Comp Power Reduction

Unit 19 Disconnected

Rack Sensor 3 Failure

Unit On

No Power

Unit 20 Disconnected

Rack Sensor 4 Failure

Unit Off

Unit Disabled

Unit 21 Disconnected

Rack Sensor 5 Failure

Standby Mode

Unit Shut Down

Unit 22 Disconnected

Rack Sensor 6 Failure

Power On

Dehum Disabled

Unit 23 Disconnected

Rack Sensor 7 Failure

Power Off

Dehum Disabled 12hrs

Unit 24 Disconnected

Rack Sensor 8 Failure

Unit 01 Disconnected

Dehum Enabled

Unit 25 Disconnected

Rack Sensor 9 Failure

Unit 02 Disconnected

Humidifier Problem

Unit 26 Disconnected

Rack Sensor 10 Failure

Unit 03 Disconnected

Dehum Hrs Exceeded

Unit 27 Disconnected

High Return Temperature

Unit 04 Disconnected

Comp 1 Pumpdown Fail

Unit 28 Disconnected

Room Humidity Problem

Unit 05 Disconnected

HCB Not Connected

Unit 29 Disconnected

Bottom Fan Failure

Unit 06 Disconnected

BMS Disconnected

Unit 30 Disconnected