Liebert iCOM

®

Control

Liebert

®

CRV

86

Figure 77 Sensor calibration / setup parameters - Page 1

Return Temperature—This parameter adjusts the return temperature reading from the actual

sensor to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Temperature—This parameter shows the adjusted temperature value of the

return sensor. This value is the actual sensor reading (+ or -) the offset “Return Temperature”.
Return Humidity—This parameter adjusts the return humidity reading from the actual sensor to

compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Humidity—This parameter shows the adjusted humidity value of the return

sensor. This value is the actual sensor reading (+ or -) the offset “Return Humidity”.
Digiscroll 1 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sensor to

compensate for any error or drift of the sensor.
Calibrated Digiscroll 1 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor

value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.

Figure 78 Sensor calibration / setup parameters - Page 2

to change parameter

for next/previous unit

to select parameter

to confirm

then

S601
S602
S603
S604
S605
U606
S607
S608
S609
S610
S611

PASSWORD Actual Level 0)

????

Return Temperature

+0°F

Calibrated Return Temperature

77°F

Return Humidity

+0.0%

Calibrated Return Humidity

26.0%

Digiscroll 1 NTC

+0°F

Calibrated Digiscroll 1 NTC

200°F

SENSOR CALIBRATION/SETUP (page 1 of 4)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then

S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622

PASSWORD Actual Level 0)

????

Return T Sensor PTC or NTC

NTC

Return T Sensor

+0°F

Calibrated Return T Sensor

°F

Supply T Sensor PTC or NTC

NTC

Supply T Sensor

+1°F

Calibrated Supply T Sensor

75°F

CW T Sensor

°F

Calibrated CW T Sensor

°F

SENSOR CALIBRATION/SETUP (page 2 of 4)

UNIT 01