Liebert iCOM

®

Control

Liebert

®

CRV

80

Figure 68 Diagnostics / service mode parameters screen - Page 2

Manual Mode—Use this setting to place the Liebert iCOM

®

control in manual mode. This is the

initial setting necessary to activate any of the following items.
Motor(s)—Setting this option to ON will start the main fan of the unit. Note that the main fan must

be On in order to activate any of the following overrides.
Compressor 1—Use this setting to turn on compressor 1 and select the mode of compressor

operation. The operation selections are RUN, EVACUATE and CHARGE.
Compressor 1 Capacity—Use this setting to enable Compressor 1 Cycle Ramp.
Compressor 1 Cycle Ramp—This setting allows the user to select the capacity the compressor

should run at. Range on this is 0 – 100%.
Compressor 1 LLSV—This option will control the liquid line solenoid valve for compressor 1.

Figure 69 Diagnostics / service mode parameters screen - Page 3

Electric Heat 1 (or HG/HW)—This will activate stage 1 of the unit’s reheat system.
Dehumidification Output—This activates the dehumidification cycle.

to change parameter

for next/previous unit

to select parameter

to confirm

then

S312
S313
S314
S315
S316
S317
S318
S319
S320
S321
S322

PASSWORD Actual Level 0)

????

Manual Mode

No

Motor(s)

On

Compressor 1

Run

On

Compressor 1 Capacity

On

Compressor 1 Cycle Ramp

76%

Compressor 1 LLSV

On

DIAGNOSTICS/SERVICE MODE (page 2 of 6)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then

S323
S324
S325
S326
S327
S328
S329
S330
S331
S332
S333

PASSWORD Actual Level 0)

????

Electric Heat 1

Off

Dehumidification Output

Off

Humidifier Fill
Humidifier Off
Humidifier Drain
Humidifier Current

A

DIAGNOSTICS/SERVICE MODE (page 3 of 6)

UNIT 01