Operation in Teamwork Mode

Liebert

®

CRV

98

11.3 Wiring a Liebert iCOM

®

U2U Network

A network switch is required to enable Ethernet unit-to-unit communication on one or more Liebert

CRV’s. Each Liebert CRV requires two straight-through Ethernet cables from a network switch. One

cable connects to port P64 on the Liebert iCOM input/output board and the other straight-through

cable connects to the P64 port on the back of the large display (see Figure 92).

Figure 91 U2U network setup diagram

Network

Switch

Liebert Cooling Unit

with Large Liebert

iCOM Display

Liebert Cooling Unit

with Large Liebert

iCOM Display

Liebert Cooling Unit

with Large Liebert

iCOM Display

Display Service /Network

Liebert iCom Display Menu

IP Address: 192.168.254.033

U2U Address: 33

Group #: 1

---------------------------------------

Display Service /Network

Liebert Cooling Unit

Control Board Menu

IP Address: 192.168.254.001

U2U Address: 1

Group #: 1

Display Service/Network

Liebert iCom Display Menu

IP Address: 192.168.254.034

U2U Address: 34

Group #: 1

---------------------------------------

Display Service/Network

Liebert Cooling Unit

Control Board Menu

IP Address: 192.168.254.002

U2U Address: 2

Group #: 1

Display Service/Network

Liebert iCom Display Menu

IP Address: 192.168.254.035

U2U Address: 35

Group #: 1

---------------------------------------

Display Service/Network

Liebert Cooling Unit
Control Board Menu

IP Address: 192.168.254.003

U2U Address: 3

Group #: 1