Operation in Teamwork Mode

97

Liebert

®

CRV

11.0 O

PERATION

IN

T

EAMWORK

M

ODE

11.1 Unit-to-Unit Network Wiring

Liebert CRV’s can be connected in a unit-to-unit, or U2U, configuration, which allows multiple units

to communicate with each other, sharing of local unit status and sensor readings. The U2U network

will allow up to 32 units to be connected within a single group and up to 99 different groups to exists

on the same physical network. Groups can be used to create zones of influence so that only the Liebert

CRV’s serving a common area will work together and back each other up.
The U2U setup unlocks the use of Lead-Lag/Rotation, Cascade and Teamwork Modes 1 and 2.
Lead-lag/rotation allows a standby Liebert CRV to activate based on an alarm or on a rotation

based on time.
Cascade provides staging of the Liebert CRV’s based on the actual temperature and its relation to

the temperature setpoint.
Teamwork Modes 1 and 2 use the collective temperature information from all Liebert CRV’s on the

U2U network within the same group to determine how the group of Liebert CRV’s should operate. To

help manage the large amount of sensor information Liebert iCOM

®

allows the sensor data to be used

as an average or a maximum value of all temperature sensor readings at both the local and system

level.
Different groups can be configured to operation in different teamwork modes. If one Liebert CRV

group serves a nonbalanced load, Teamwork Mode 2 will share all sensor data, prevent conflicting

modes of operation between units but still allow each Liebert CRV to modulate based on the unit’s

local sensor readings. Another group of Liebert CRV’s can be configured to operate in Teamwork

Mode 1 that will share all sensor data, prevent conflicting modes of operation between units but will

modulate all Liebert CRV’s at the same capacity based on the U2U sensor readings.

11.2 Liebert iCOM U2U Ethernet Network

The Liebert iCOM U2U network must be isolated from other network traffic. The network switch(es)

that connect Liebert iCOM controls must be dedicated to supporting only Liebert iCOM

communication. The U2U network cannot be connected to the building or IT network. If network

communication is ever lost, all Liebert iCOM-controlled cooling units will continue to operate as

independent units.
The Liebert iCOM control can support up to 64 nodes on one network. An input/output board, large

display and large wall-mount display are each considered one node. Of the 64 nodes that may be

connected, no more than 32 may be input/output boards (32 cooling units).
Network communication can be configured during system startup by a Liebert-trained technician. For

technical issues contact: