Liebert iCOM

®

Control

Liebert

®

CRV

88

Figure 80 Sensor calibration / setup parameters - Page 4

This unit can be equipped with a total of 20 rack sensor readings or 10 2T temperature sensor

modules. This menu provides the ability to calibrated by entering a negative or positive offset. The

calibrated reading is displayed in the far right column. If a value is not shown in the far right column,

then the sensor is either not setup correctly or is not connected.

Figure 81 System / network setup parameters—System - Page 1

Number of Connected Units—This parameter sets the number of units that will be viewable from

the large display and will participate on the unit to unit network.
Teamwork Mode—This parameter selects which teamwork mode to use within a selected group.

Teamwork modes are described in section 4.0 of this manual.
Teamwork Mode 1 based on
Configuration Safe—This parameter saves or loads configuration settings for the display that have

been modified from the factory defaults to an internal file that can be downloaded / uploaded using

the Liebert iCOM

®

Service Tool. Selecting “Save” will write the settings to the internal storage file

and selecting “Load” will write the settings from the internal storage file to the application software.

The internal file is updated every 12 hours automatically.

to change parameter

for next/previous unit

to select parameter

to confirm

then

S634
S635
S636
S637
S638
S639
S640
S641
S642
S643
S644

PASSWORD Actual Level 0)

????

Rack Temperature Sensor 1B

°F

77°F

Rack Temperature Sensor 2B

°F

78°F

Rack Temperature Sensor 3B

°F

77°F

Rack Temperature Sensor 4B

°F

77°F

Rack Temperature Sensor 5B

°F

78°F

Rack Temperature Sensor 6B

+0°F

°F

Rack Temperature Sensor 7B

+0°F

°F

Rack Temperature Sensor 8B

+0°F

°F

Rack Temperature Sensor 9B

+0°F

°F

Rack Temperature Sensor 10B

+0°F

°F

SENSOR CALIBRATION/SETUP (page 4 of 4)

UNIT 01

S801
S802
S803
S804
S805
S806
S807
S808
S809
S810
S811

PASSWORD

(Actual Level 0)

????

Number of Connected Units

1

Teamwork Mode

No

Teamwork Mode 1 based on

Configuration Safe

OK

No

Network Safe

OK

No

SW Version

CRB 2.00.006.STD

SYSTEM / NETWORK SETUP (page 1 of 2)

SYSTEM

to change parameter

for next/previous unit

to select parameter

to confirm

then