Refrigerant Connections

Liebert

®

CRV

22

Table 9

Piping and refrigerant sizes for Liebert air-cooled, VFD control condensers with R-410A

Condenser Piping Connection Sizes, Cu, O.D.

Condenser Model #

Entering Hot Gas

Line, in. (mm)

Returning Liquid

Line, in. (mm)

TCSV28K

1-1/8 (28.6)

7/8 (22.2)

TCSV60K

1-1/8 (28.6)

7/8 (22.2)

TCSV90K

1-1/8 (28.6)

7/8 (22.2)

Source: DPN001624, Rev. 5, Page 3

Table 10

Recommended refrigerant line sizes for Liebert air-cooled, VFD control condensers
with R-410A, Cu, OD

Liebert CRV Model #

Total Equivalent

Length, ft. (m)

Hot Gas Line,

in. (m)

Liquid Line,

in. (m)

CR020RA

50 (15.2)

3/4 (19.1)

5/8 (15.9)

100 (30.5)

3/4 (19.1)

5/8 (15.9)

150 (45.7)

3/4 (19.1)

5/8 (15.9)

300 (91.4)

7/8 (22.2)

2

3/4 (19.1)

CR035RA

50 (15.2)

7/8 (22.2)

3/4 (19.1)

100 (30.5)

7/8 (22.2)

3/4 (19.1)

150 (45.7)

7/8 (22.2)

3/4 (19.1)

300 (91.4)

1-1/8 (28.6)

2

7/8 (22.2)

1. Consult factory for proper line sizing for runs longer than 300 ft. (91.4m) equivalent length.
2. Must downsize vertical riser one trade size (1-1/8" to 7/8" or 7/8" to 3/4" ).
Source: DPN001624, Rev. 5, Page 3