Piping

15

Liebert

®

CRV

5.1.1 Condensate Piping—Field-Installed

• Do not reduce drain lines
• Do not expose drain line to freezing temperatures
• Drain line may contain boiling water. Use copper or other suitable material
• Drain line must comply with local building codes
• Emerson recommends installing under-floor leak detection equipment

Gravity Drain—Units Without Factory-Installed Condensate Pump

• 3/4" FPT drain connection is provided on units without optional factory-installed condensate

pump with infrared humidifier or no humidifier; 1-1/4" FPT connection is provided on units with

steam generating humidifier

• Pitch the drain line toward the drain a minimum of 1/8" (3mm) per 1 foot (305mm) of length
• Drain is trapped internally. Do not trap the drain external to equipment
• Drain line must be sized for 2 gpm (7.6 l/m) flow

NOTICE

Risk of improper piping connections. Can cause damage to the equipment and to the building.
The drain line has an internal trap and must not be trapped outside the unit or water may

back up into the drain pan and overflow the unit cabinet.

Figure 13 Gravity drain

Condensate Pump

• 1/2" copper sweat connection is provided on units with optional factory-installed condensate

pump

• Condensate pump is rated for approximately 6 GPM (22.7 l/min) at 30 ft (9m) total head
• Size piping based on available condensate head

5.1.2 Humidifier Supply Water—Optional Steam Generating Canister

• 1/4" supply line; maximum water pressure is 145psi (1000kPa)
• Fill valve is sized for pressure range of 30 to 120psi (207-827kPa)
• Do not supply steam generating humidifier with softened water
• Do not use hot water source
• Water conductivity must be in the range of 330-670 micro-siemens

CORRECT

INCORRECT

UNIT

Internal
Drain

External
Drain

Continuous Downward Slope

Internal
Drain

UNIT

UNIT

External
Drain

Internal
Drain

External
Drain

These are external traps also, although
unintentional. Lines must be rigid enough
not to bow over top of other objects.

INCORRECT

Do Not Externally
Trap the Unit

DPN001556
Rev. 0