Figure 83 System/Network setup parameters Unit- Page 1

Monitoring Address—This parameter sets the address used by the Liebert IntelliSlot

®

cards. This

is set to 3 from the factory and should not be changed.
Monitoring Timeout/Handshake—This parameter can be used with a building management

system to verify communications has not been lost between the Liebert iCOM

®

control and the BMS.

If the amount of time specified in this parameter elapses before the BMS writes a new value then an

alarm will occur “BMS TIMEOUT” and the temperature setpoint will revert to the backup setpoint

and the fan speed “if equipped” will change to 100%. To disable this feature write a zero to this

parameter when it is active.
Unit Name—This parameter is a label to identify the unit from the local or remote display. This label

will show at the top right of every screen that has monitoring or configuration of that unit.
Configuration Safe—This parameter saves or loads configuration settings for the control board that

have been modified from the factory defaults to an internal file that can be downloaded / uploaded

using the Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage

file and selecting “Load” will write the settings from the internal storage file to the application

software. The internal file is updated every 12 hours automatically.
Network Safe—This parameter saves or loads network settings for the control board that have been

modified from the factory defaults to an internal file that can be downloaded / uploaded using the

Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and

selecting “Load” will write the settings from the internal storage file to the application software.
SW Version—This parameter contains the application software version loaded onto the Liebert

iCOM control board.

S823
S824
S825
S826
S827
S828
S829
S830
S831
S832
S833

PASSWORD

(Actual Level 0)

????

Monitoring Address

3

Monitoring Timeout /Handshake

No/

0

Unit Name

UNIT

Configuration Safe

Changed

No

Network Safe

OK

No

SW Version

CRM 2.00.006 .STD

SYSTEM / NETWORK SETUP (page 1 of 2)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then