Maintenance

Liebert

®

CRV

110

To extract the filters (refer to Figure 97:
1. Push up the upper filter.
2. Pull the bottom of the filter away from the Liebert CRV.
3. Pull it out of the unit.
4. Lift the lower filter up
5. Pull the bottom of the filter away from the Liebert CRV.
6. Pull it out of the unit.

Figure 97 Remove the air filters

After cleaning or replacing the filter and before reassembling the unit, check that the air differential

pressure switch pipes (clogged filter alarm) are in the correct position and order. Check also that the

drain trays are clean and the pipe secure.

Figure 98 Differential pressure switch tubes

Before restarting the unit, be sure that the microswitches are properly closed; otherwise, the unit

remains in safety status.

Push the upper filter up, pull the

bottom away from the Liebert CRV and

lift it out of the unit

Slide the lower filter up beyond the support

bar and lift it out of the Liebert CRV the

same way as the upper filter

Upper Filter

Lower Filter

Support Bar

Differential

pressure

switch tube

Advertising