Liebert iCOM

®

Control

79

Liebert

®

CRV

Figure 67 Diagnostics / service mode parameters screen - Page 1

HP 1 Alarm Code—Compressor 1 high pressure alarm code.
LP 1 Alarm Code—Indicates which phase compressor 1 is operating in. For more information on

this refer to the Liebert iCOM

®

Training and Service manual’s low pressure transducer flow chart.

HT 1 Alarm Counter—Compressor 1 high temperature event alarm counter. If more than five

events in a rolling 4 hour period occur then the compressor will be locked out.
12h Dehum Counter—
Low Supply Temperature Counter—
Actual LP1 Pressure
—Current refrigerant low pressure side reading in atmosphere for

Compressor 1.
Actual HP1 Pressure—Current refrigerant high pressure side liquid reading in atmosphere for

Compressor 1. (This is available only on water cooled units equipped with motorized ball valves.)

to change parameter

for next/previous unit

to select parameter

to confirm

then

S301
S302
S303
S304
S305
S306
S307
S308
S309
S310
S311

PASSWORD Actual Level 0)

????

HP 1 Alarm Code

0

LP1 Alarm Counter

0

HT1 Alarm Counter

0

12h Dehum Counter

0

Low Supply Temperature Counter

0

Actual LP1 Pressure

169psig

Actual HP1 Pressure

338psig

DIAGNOSTICS/SERVICE MODE (page 1 of 6)

UNIT 01