6.2.1 General Layout

1. Piping must be Type ACR copper tubing and sized per Tables 7, 8, 9 and 10.

Use the shortest possible refrigeration pipelines to minimize the total charge of refrigerant and

the number of pressure drops.

2. Minimize the number of bends and make the bends the largest radius practical to prevent

constricting refrigerant flow.

3. Insulate the piping as specified in Table 5. If the pipes are installed next to electrical cables, they

must be isolated from the building using vibration-isolating supports to avoid damage to cable

insulation.

4. There must be at least one inch (25mm) separation between the gas and liquid pipelines. If this is

not possible, insulate both lines.

5. Support both horizontal and vertical pipes with vibration-damping clamps, which include rubber

gaskets. Place these clamps every 5 to 7 ft. (1.5 to 2m).

NOTE
All field-installed piping must comply with applicable national, state and local codes.

Table 5

Condenser positioning

Condenser

Position

Condenser Above

Liebert CRV

Condenser and

Liebert CRV

at Same Level

Condenser Below

Liebert CRV

(Not Recommended)

Insulation

Discharge

Line

Indoor

necessary

necessary

necessary

Outdoor only for aesthetic reasons

only for aesthetic reasons

only for aesthetic reasons

Liquid

Line

Indoor only for aesthetic reasons

only for aesthetic reasons

no (expose to cold under-floor air)

Outdoor only for aesthetic reasons

only if exposed to sun

only if exposed to sun

Layout

** See Table 6

Table 6

Liebert CRV position relative to the remote condenser

Parameter

Maximum Distances, ft. (m)

From Liebert CRV to condenser

300 (91.4) equivalent length

From Liebert CRV to VFD condenser

Above: 60 (18.3)

Below: 15 (4.5)

From Liebert CRV to Liebert Lee-Temp

condenser

Above: 60 (18.3)

Below: 0 (0)

Requirements
Oil traps on vertical line of gas refrigerant

Every 15 (4.6)

15 ft. (4.6m)

(See *)

Gas

Liquid

* Oil traps every 15 ft. (4.6m)

of vertical piping

Room Unit

(See **)

Gas

Liquid

Room Unit

Liquid

Room Unit

(See**)