Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 51

Advertising
background image

Startup

43

Liebert

®

CRV

To adjust the baffles:
1. Open the door containing the Liebert iCOM

®

display.

2. Remove the two screws holding a baffle panel segment in place.
3. Slide out the baffle segment.
4. There is one screw on each side of the baffle, as shown in Figure 31. Remove the screws and

rotate the baffle segment around its horizontal axis to change the airflow direction.

5. Reinsert the baffle segment and reinstall the screws.

Figure 31 Adjust the baffles to ensure correct airflow direction

A blocker plate inside the display door should also be adjusted to direct air towards the racks the

Liebert CRV is intended to condition. The blocker plate can be installed on the left or right side of the

display door, or it can be removed to discharge air left and right.

1. Open Liebert

CRV Display Door

Inside view, showing

baffle removal for changing

airflow direction

2. Remove two bolts

3. Tilt and lift

baffle panel

For proper operation, the baffles

must be installed so the discharge

air points upward

DPN001863

Pg. 1, Rev. 2

Advertising