14.2 Spare Parts

Only original spare parts made by Emerson Network Power may be used. Using third-party material

can invalidate the warranty. When making seeking technical assistance, always refer to the

component list supplied with the equipment, and specify the model number, serial number and, if

available, the part number.

14.3 Maintenance Schedule

Conduct monthly, quarterly, biannual and annual checks according to the following guidelines.
All tasks and time periods listed here are the manufacturers’ regulations and must be documented in

an inspection report.

NOTE
1. When replacing a faulty component, follow the relevant manufacturer instructions.
2. When the spare parts must be brazed, be careful not to damage the internal parts (gaskets,

seals, O-rings, etc.).

Table 28

Maintenance schedule

Component

Maintenance Period

Monthly

By User

Every

3 Months

Every

6 Months

Annually

General

Check unit display for clogged-filter warning

X

Check for irregular noise from unit fans

X

Check for irregular noise from compressor (if

applicable)

X

Check for irregular noise from remote

condenser fan(s) (if applicable)

X

Filters

Check state of filters

X

Replace air filter if necessary

X

Check filter switch functionality

X

Blowers

Verify impellers move freely

X

Check bearings

X

Check motor mounts for tightness

X

Check fan safety switch

X

Electrical/Electronics

Check condition of contacts

X

Check electrical connections

X

Check operation of controller

X

Check unit operation sequence

X

Steam-Generating

Humidifier

Check cylinder and pan

X

Check condition of steam hoses

X

Verify filling solenoid valve is operating properly

X

Cooling Water Circuit

(Water/Glycol and

Chilled Water Units)

Check circuit for leakage/general condition

X

Check water (glycol) inlet temperature

X

Check water regulating valve operation

X

Check in/out water (glycol)

Δ

t

X

Check mixture glycol level (if applicable)

X