Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 101

Advertising
background image

Liebert iCOM

®

Control

93

Liebert

®

CRV

Figure 87 Rack Setup, Page 2

The Rack Setup display allows creating a graphical map of the remote rack sensors.
When the Assigned Sensors 1-6 are selected, it will drop the user down to assign the sensor node

address to the first group of six “boxes.” Setting “CRV” instead of a number (CRV is located below 0)

will give the hard-coded name “CRV” to the selected box.
A sensor address (#1- #10) or “CRV” can be assigned only once per screen.
The names for each rack can be assigned on the next page. Once names have been assigned, they will

also show up on this page (read only).

Figure 88 Rack Setup, Page 3

The Rack Setup display allows naming each rack with up to four characters, either letters or digits

(A-Z or 0-9). Names can be assigned to each rack except those that have no sensor (#0-#10), no “CRV”

or “Rack w/o sensor (-2)” assigned on the previous Rack Setup page.
When the Assigned Names 1-6 are selected, it will drop the user down to assign the rack name to the

first group of six “boxes.”

Use the navigation keys to move from rack to rack .
Enter to select a rack, and up - or down keys to scroll through
options .

RACK SETUP (page 2 of 3)

UNIT 01

Liebert CRV = CRV
No Sensors

= -2

No Rack

= 0

Sensor Node = 01-10

Assign Sensors: 01-06

07-12
13-18
19-22

Cold Aisle

1

0

0

0

0

0

0

2

3

4

0

0

5

6

0

0

0

0

0

0

0

0

CC21

Use the navigation keys to move from rack to rack .
Enter to select a rack, and up - or down keys to scroll through
options .

RACK SETUP (page 3 of 3)

UNIT 01

Liebert CRV = CRV
No Sensors

= -2

No Rack

= 0

Sensor Node = 01-10

Assign Sensors: 01-06

07-12
13-18
19-22

Cold Aisle

1

0

0

0

0

0

0

2

3

4

0

0

5

6

0

0

0

0

0

0

0

0

EC50 EC51

CC21

BB01 BB02 BB03

Advertising