Liebert iCOM

®

Control

Liebert

®

CRV

74

Figure 62 Wellness basic settings screen- Page 1

Maintenance Frequency Per Year—This parameter sets the number of expected maintenance

visits in a one year time span.
Max Bonus—This parameter will increase the time to the next maintenance cycle. A bonus should be

assigned when a service visit finds that all components are working optimally.
Max Penalty—This parameter will decrease the time to the next maintenance cycle. A penalty

should be used when a service visit finds excessive wear on components.
Last Maintenance—This parameter is set during the service call. It also indicates to other service

personnel the date of the last visit.
Service Engineer—This parameter provides a label for the service representative to list either the

company name or representative’s name.
Confirm PM—This parameter confirms that the service representative has completed the preventive

maintenance and resets the next maintenance date.
Calculated Next Maintenance—This parameter provides a date to when the next expected

maintenance should take place based on the last confirmed PM, component starts, run hours and the

penalty / bonus currently set in the Liebert iCOM

®

control.

S001
S002
S003
S004
S005
S006
S007
S008
S009
S010
S011

PASSWORD

(Actual Level 0)

????

Maintenance Frequency Per Year

1

Max Bonus

0

Max Penalty

0

Last Maintenance

06/14/2010

Service Engineer

Nobody

Confirm PM

No

Calculated Next Maintenance

06/2011

WELLNESS basic settings (page 1 of 5)

SYSTEM

to change parameter

for next/previous unit

to select parameter

to confirm