Electrical Field Connections Descriptions

125

Liebert

®

CRV

NOTICE

Risk of improper input power. Can cause equipment damage.
The electronically commutated motors included in the Liebert CRV unit are suitable for

connection to an electrical service providing input power to the unit with 300V or less line-to-

ground potential only.
Acceptable unit input electrical service for 460V (480V) nominal units:
• 480V wye with solidly grounded neutral and 277V line-to-ground
Unacceptable unit input electrical service for 460V (480V) nominal units
• Wye with high resistance (or impedance) ground
• Delta without ground or with floating ground
• Delta with corner ground
• Delta with grounded center tap

Figure 104 Electrical field connections

DPN001884
Page 3, Rev. 4

3

4

7

1

Unit
Base

2

5, 6

Typically, 2

9

9

13

11

14

12

10

8

Not
Used

Not
Used

12

15

4

Unit Top

OVERLOAD PROTECTORS

CONTACTORS

UNIT

DISCONNECT

SWITCH

2-1/2" (64mm) K.O.

1-3/32" (28mm) K.O.

1-3/4" (44.5mm) K.O.

Refer to C.1 Standard Electrical Connections and

C.2 Electrical Connections for Optional Features for

keys to numbered components.