Figure 60 Setpoints parameters screen - Page 4

MIN at CFC for EC Fan—This parameter can provide an offset to the minimum fan speed at the

minimum call for cooling. When set to 0 / 100 the MIN speed is reached when the call for fan is at 0%;

and the STD speed is reached when the call for fan reaches 100%.
For example, if the minimum is set to 20 and the standard is set to 90, the fan speed MIN is reached

earlier (the fan operates on lower speed compared to the calculated call for fan), and the STD speed is

reached faster when compared to the calculated call for fan.
STD at CFC for EC Fan—This parameter can provide an offset to the minimum fan speed at the

minimum call for cooling. When set to 0 / 100 the MIN speed is reached when the call for fan is at 0%;

and the STD speed is reached when the call for fan reaches 100%.
High Temp Limit Approach—This parameter sets the sensor that controls the fan speed maximum

override. This can be set to Disable, Supply or Return.

High Temp Limit Approach at— This parameter sets the temperature when the units fan speed

can operate above the maximum speed. The maximum override speed during this mode is set in

parameter A157 (Advanced menus).
Ball Valve Setpoint Offset—This parameter adjusts the operating compressor discharge pressure

by changing the targeted range of control. Available only on water-cooled units.

Unit Diary—Large Display Only

Shows all entered program changes and maintenance performed on the unit.

NOTE
The Liebert CRV fans are oversized and can be used to help protect equipment in emergency

situations, such as high temperature and a single fan failure.

Table 26

Unit diary parameters

Function

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1
Text entered with iST

(Liebert iCOM

®

Service Tool)

N/A

-

S134
S135
S136
S137
S138
S139
S140
S141
S142
S143
S144

PASSWORD (Actual Level 0)

????

MIN at CFC for EC Fan

0%

STD at CFC for EC Fan

100 %

High Temp Limit Approach

Supply

High Temp Limit Approach at

2°F

Ball Valve Setpoint Offset

0psig

SETPOINTS (page 4 of 4)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then