Figure 42 liebert icom® default screen symbols, 1 navigating through the liebert icom menus, 1 control interface – Emerson Liebert CRV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 C R 0 2 0 R A 1 C 7 S D 1 8 1 1 E L 1 0 P A User Manual

Page 60: 2 accessing submenus, Accessing submenus on large displays, Navigating through the liebert icom menus, 1 control interface 10.1.2 accessing submenus, Liebert icom

Advertising
background image

Liebert iCOM

®

Control

Liebert

®

CRV

52

Figure 42 Liebert iCOM

®

default screen symbols

10.1 Navigating Through the Liebert iCOM Menus

Liebert iCOM shows icons and text for monitoring and controlling your Liebert cooling units or

network of cooling units. The number of icons and amount of text shown depends on the display size.

10.1.1 Control Interface

When the buttons on the Liebert iCOM control have not been pressed for a short period, the display

backlight turns off. Pressing any key will turn the backlight on (wake up the screen) and display the

Status menu of the last cooling unit viewed. The Status menu will show the cooling unit’s operational

mode(s), return air temperature and humidity readings, temperature and humidity setpoints and any

active alarm conditions.
If the cooling unit has a large display and is not on a network, whether it is networked or stand-alone,

the Status menu will display only that cooling unit’s information. Any large display that is connected

to a network can be used to view any cooling unit on the network or show an average view of the

entire system of cooling units.
The Liebert iCOM control has three main menus: User, Service and Advanced.
The User menu contains the most frequently used features, settings and status information. The

Service menu contains settings and features used to set up unit communications and for unit

maintenance. The Advanced menu contains settings used to set up the unit at the factory.

10.1.2 Accessing Submenus

To access the User, Service or Advanced menu, press the Enter or down arrow key while viewing the

Status menu of the unit you wish to access. The User menu will be displayed first. To view the Service

or Advanced menus, press the right arrow key.

Accessing Submenus on Large Displays

While viewing the menu you wish to access (User, Service or Advanced), press the enter key to

highlight the first icon. Use the arrow keys to navigate through the icons. With the desired icon

highlighted, press the enter key to enter that submenu. Once in a Submenu, a list of parameters will

be displayed.
The up and down arrow keys may be used to scroll through the parameters page-by-page if the

submenu has multiple pages. To scroll item-by-item, press the Enter key and then use the up and

down arrow keys. Using the right or left arrow keys on large displays attached to a network will

NOTE
Menu settings may be viewed without a password, but changing settings requires a password.

If a password is required, Liebert iCOM shows a prompt to enter the password. The password

for the User menu is 1490. The password for Service menu is 5010. For details on entering a

password, see Entering a Password on page 53

fan

cooling

maintenance

hot water

electric heat

dehumidification

humidification

freecooling

Advertising