71

Liebert

®

CRV

Figure 59 Setpoints parameters screen - Page 3

Fan Control Type—This parameter sets how the fan speed will be controlled. This parameter can be

set to Auto mode, which will allow the Liebert CRV to drive the fan based on the temperature sensor

selected for sensor control type. This parameter can also be set to Manual mode, which allows the

Liebert CRV to be set to a fixed fan speed either through the local display or through a building

management system.
Fan Control Sensor—This parameter sets which sensor will drive the Liebert CRV fans when set to

Auto mode for the fan control type.
Fan Regulation Type—This parameter is the fans’ control type. It can be set to Proportional

control, which will modulate the fans linearly based on the deviation from the setpoint. PI control is

also available and works in the same manner as the temperature control integral term.
Fan Delta—This parameter sets the fan speed setpoint. The delta accounts for the temperature rise

from the Supply Air Sensor and the Remote Rack sensors by adding the Fan Delta to the

Temperature Setpoint (S102). This eliminates the possibility of setting the remote rack temperature

setpoint lower than the supply temperature setpoint.
Fan Speed Proportional Band—This parameter adjusts the fans rate of change based on the

actual sensor values deviation from setpoint or the delta. The smaller this number the faster the fan

will increase its speed. Too small of a number may cause the fans to excessively reposition.
Fan Speed Integration—This parameter adjusts the fanspeed of the unit based on time away from

setpoint. This parameter is only active when Control Type is set to “PI.”
Fan Speed Manual Setpoint—This parameter sets the speed of the fans when the unit is placed

into Manual Fan Speed Control mode.
Fan Speed STD—This parameter sets the maximum fan speed of the unit under normal operating

circumstances.
Fan Speed Min—This parameter sets the lowest fan speed operation of the unit.
Fan Speed Dehum—This parameter sets the fan speed the unit will operate at during a call for

dehumidification. The fan speed will position to the highest requirement. If the call for fan speed from

the remote rack sensor is requesting more CFM than the Dehum fan speed, then the fans will run at

the remote sensor fan speed request.

S123
S124
S125
S126
S127
S128
S129
S130
S131
S132
S133

PASSWORD (Actual Level 0)

????

Fan Control Type

Auto

Fan Control Sensor

Remote Sensor

Fan Regulation Type
Fan Delta

°F

Fan Speed Proportional Band

°F

Fan Speed Integration

min

Fan Speed Manual Setpoint

%

Fan Speed STD

75%

Fan Speed Min

50%

Fan Speed Dehum

70%

SETPOINTS (page 3 of 4)

UNIT 01

to change parameter

for next/previous unit

to select parameter

to confirm

then