Electrical Data

123

Liebert

®

CRV

A

PPENDIX

B - E

LECTRICAL

D

ATA

NOTICE

Risk of exceeding line-to-ground limit. Can cause equipment damage.
The electrically commutated (EC) motors included in 480V CR035 and CR040 units are

suitable for connection to power supplies with 300V or less line to ground potential. Excess

line-to-ground voltage can cause capacitor failure internal to the motors.
• Power supplies such as 480V WYE with solidly grounded neutral have 277V line to ground

and are acceptable.

• Power supplies such as 480V WYE with high resistance (or impedance) ground, 480V delta

without ground or with floating ground, 480V delta with corner ground or 480V delta with

grounded center tap will exceed the 300V line-to-ground limit.

Table 32

Liebert CRV electrical data - 60Hz (Amps)

Voltage

Air-Cooled Units

Water/Gylcol-Cooled Units

Chilled Water Units

CR035RA

CR020RA

CR035RW

CR020RW

CR040RC

460/3/60 208/3/60 460/3/60 208/3/60 460/3/60 208/3/60 460/3/60 208/3/60

460/3/60

208/3/60

Cooling with Dehumidifying, Condensate Pump, Reheat; with or without Humidifier

FLA

31.7

62.0

24.3

51.0

31.7

62.0

24.3

51.0

11.7

24.9

WSA

38.6

75.4

29.3

61.6

38.6

75.4

29.3

61.6

14.6

31.1

OPD

50

100

35

80

50

100

35

80

20

35

Cooling with Dehumidifying, Condensate Pump and Humidifier; NO Reheat

FLA

27.9

53.8

20.5

42.8

27.9

53.8

20.5

42.8

7.9

16.7

WSA

32.9

63.1

23.6

49.3

32.9

63.1

23.6

49.3

9.9

20.9

OPD

50

90

35

70

50

90

35

70

15

25

Cooling with Dehumidifying and Condensate Pump, NO Reheat, NO Humidifier

FLA

24.2

45.4

16.8

34.4

24.2

45.4

16.8

34.4

4.2

8.3

WSA

29.2

54.7

19.9

40.9

29.2

54.7

19.9

40.9

4.6

9.1

OPD

45

90

30

60

45

90

30

60

15

15

Cooling with Dehumidifying and Reheat; NO Condensate Pump, NO Humidifier

FLA

30.5

59.7

23.1

48.7

30.5

59.7

23.1

48.7

10.5

22.6

WSA

37.4

73.1

28.1

59.3

37.4

73.1

28.1

59.3

13.1

28.3

OPD

50

100

35

80

50

100

35

80

15

30

Cooling with Dehumidifying, NO Condensate Pump, NO Reheat, NO Humidifier

FLA

23.0

43.1

15.6

32.1

23.0

43.1

15.6

32.1

3.0

6.0

WSA

28.0

52.4

18.7

38.6

28.0

52.4

18.7

38.6

3.4

6.8

OPD

45

80

30

60

45

80

30

60

15

15

Table 33

Calibration of electrical components

Refrigeration Circuit

Item No.

Component

Setting

Notes

Contact

18-19

High Pressure

Transducer

Range 045 barg

Output 05V

See Liebert iCOM

®

User Manual, SL-18835

14

Low Pressure

Transducer

Range 017.3 barg

Output 05V

3

High Pressure

Switch (HP)

STOP 38.7±1 barg

START 30.0±1.5 barg

(fixed setting manual reset)

Reset

Normally

Closed

Clogged Filter

Differential Pressure

Switch (CF)

Setpoint range 0.54 mbar

Filter G4 = 2 mbar

Setting Ring

Normally

Closed