Liebert iCOM

®

Control

Liebert

®

CRV

94

Figure 89 Options setup parameters - Page 1

Low Pressure Alarm Delay—This parameter sets the amount of time that the unit will ignore a

low pressure condition. In the past this parameter has also been referred to as a Winter Start Time.

This parameter can be set between 0 to 5 minutes.
Electric Stages—This parameter shows the number of electric stages that can be activated during a

call for reheat. This parameter is setup from the factory based on the model number of the unit.
3P Actuator Runtime—If Valve Control is selected for “Time” then this parameter sets the travel

time of the valve to determine the full open and closed position of the valve. This setting is set from

the factory based on the valves manufacturer specifications.
3P Actuator Direction—This parameter selects if the valve is a “Direct” or “Reverse” acting valve.

Note

NOTE
When attaching the optional leak detection sensors (Liebert Liqui-tect

®

) the following

parameters must be adjusted:

• S408 – Set to LQTECH
• S409 – Set to alarm

to change parameter

for next/previous unit

to select parameter

to confirm

then

S401
S402
S403
S404
S405
S406
S407
S408
S409
S410
S411

PASSWORD Actual Level 0)

????

Low Pressure Alarm Delay

1min

Electric Stages

1

Heater ON at CFC

-66 %

Water Detector

No

Water Detector Function
3P Actuator Runtime

sec

3P Actuator Direction

OPTIONS SETUP (page 1 of 2)