Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 109

Advertising
background image

Bit

Hex

Dec

Alarm word

Alarm word 2 Warning word Warning word

2

Extended

Status word

Extended

Status word 2

Alarm Word Extended Status Word
18

00040000

262144

Brake

Overload

(A26)

Fans error

Brake

Overload

(W26)

Fans Warn

Password

Protection 0–

61 =

ALL_NO_ACCE

SS OR

BUS_NO_ACC

ESS OR

BUS_READON

LY

Start

19

00080000

524288

U phase Loss

(A30)

ECB error

Brake Resistor

(W25)

ECB Warn

Reference

High
reference > 4–

55

Start Applied

20

00100000

1048576

V phase Loss

(AA31)

reserved

Brake IGBT

(W27)

reserved

Reference Low
reference < 4–

54

Start delay

21

00200000

2097152

W phase Loss

(A32)

reserved

Speed Limit

(W49)

RESERVED

Local

Reference
reference site

= REMOTE >

auto on

pressed &

active

Sleep

22

00400000

4194304

Fieldbus Fault

(A34)

reserved

Fieldbus Fault

(W34)

reserved

Protection

mode

notification

Sleep Boost

23

00800000

8388608

24 V Supply

Low (A47)

reserved

24V Supply

Low (W47)

reserved

Unused

Running

24

01000000

16777216

Mains Failure

(A36)

reserved

Mains Failure

(W36)

reserved

Unused

Drive Bypass

25

02000000

33554432

1.8V Supply

Low (A48)

Current Limit

(W59)

Current Limit

(A59)

reserved

Unused

Fire Mode

26

04000000

67108864

Brake Resistor

(A25)

reserved

Low Temp

(W66)

reserved

Unused

Pump Protect

27

08000000

134217728

Brake IGBT

(A27)

reserved

Voltage Limit

(W64)

reserved

Unused

Firemode

Limit Exceed

28

10000000

268435456

Option

Change (A67)

reserved

Encoder loss

(W90)

reserved

Unused

FlyStart active

29

20000000

536870912

Drive

Initialized

(A80)

Encoder loss

(A90)

Output freq.

lim. (W62)

BackEMF too

High

Unused

30

40000000

1073741824 Safe Stop

(A68)

PTC

Thermistor

(A74)

Safe Stop

(W68)

PTC Thermist

or (W74)

Unused

31

80000000

2147483648 Mech. brake

low (A63)

Dangerous

failure (A72)

Extended

Status Word

Protection

Mode

The alarm words, warning words and extended status words can be read out via serial bus
or optional fieldbus for diagnostics, or through 16–94 Ext. Status Word.

Warnings and alarms

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

107