Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 127

Advertising
background image

Frequency type designation

0150

0200

0250

0300

0400

Continuous (3 x 440–480) [A]

21

27

34

40

52

Intermittent (3 x 440–480 V) [A]

23.1

29.7

37.4

44

61.6

Continuous kVA (400 V AC) [kVA]

16.6

22.2

26

30.5

42.3

Continuous kVA (460 V AC) [kVA]

16.7

21.5

27.1

31.9

41.4

Maximum input current
Continuous (3 x 380–439 V) [A]

22

29

34

40

55

Intermittent (3 x 380–439 V) [A]

24.2

31.9

37.4

44

60.5

Continuous (3 x 440–480 V) [A]

19

25

31

36

47

Intermittent (3 x 440–480 V) [A]

20.9

27.5

34.1

39.6

51.7

Additional specifications
Estimated power loss at rated maximum load [W]

4)

278

392

465

525

698

IP20 maximum cable cross-section (mains, motor, and load sharing)

16, 10,- (8, 8,-)

25,-,- (2,-,-)

25 (2)

IP21, IP55, IP66 maximum cable cross section (mains, motor) [mm

2

/

(AWG)]

10, 10, 16 (6, 8, 6)

35, 25, 25 (2, 4, 4)

50 (1)

IP21, IP55, IP66 maximum cable cross-section (brake, load sharing)

[mm

2

/(AWG)]

10, 10,- (8, 8,-)

35,-,- (2,-,-)

50 (1)

With mains disconnect switch included:

16/6

Weight enclosure IP20 [kg]

12

12

12

23.5

23.5

Weight enclosure IP21 [kg]

23

23

23

27

27

Weight enclosure IP55 [kg]

23

23

23

27

27

Weight enclosure IP66 [kg]

23

23

23

27

27

Efficiency

3)

0.98

0.98

0.98

0.98

0.98

Table 37: Mains supply 3 x 380–480 V AC — Normal overload 110% for 1 minute, 50HP - 125HP

Frequency type designation

0500

0600

0750

1000

1250

Typical shaft output [HP]

50

60

75

100

125

Typical shaft output [HP] at 460 V

50

60

75

100

125

IP20/Chassis

6)

B4

C3

C3

C4

C4

IP21/NEMA 1

C1

C1

C1

C2

C2

IP55/Type 12

C1

C1

C1

C2

C2

IP66/NEMA 4X

C1

C1

C1

C2

C2

Output current
Continuous (3 x 380–439 V) [A]

73

90

106

147

177

Intermittent (3 x 380–439 V) [A]

80.3

99

117

162

195

Continuous (3 x 440–480 V) [A]

65

80

105

130

160

Intermittent (3 x 440–480 V) [A]

71.5

88

116

143

176

Continuous kVA (400 V AC) [kVA]

50.6

62.4

73.4

102

123

Continuous kVA (460 V AC) [kVA]

51.8

63.7

83.7

104

128

Maximum input current
Continuous (3 x 380–439 V) [A]

66

82

95

133

161

Intermittent (3 x 380–439 V) [A]

72.6

90.2

106

146

177

Continuous (3 x 440–480 V) [A]

59

73

95

118

145

Intermittent (3 x 440–480 V) [A]

64.9

80.3

105

130

160

Additional specifications

Technical Specification

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

125

Advertising