Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 12

Advertising
background image

• Using a digital input and the 10V as a power supply.

• Parameter set-up:

• Set 1-90 Motor Thermal Protection to Thermistor Trip [2]
• Set 1-93 Thermistor Source to Digital Input 19 [4]

• Using an analog input and 10V as a power supply

• Parameter set-up:

• Set 1-90 Motor Thermal Protection to Thermistor Trip [2]
• Set 1-93 Thermistor Source to Analog Input 54 [2]. Do not use Analog Input

54 as any other feedback or reference source. Be sure to configure the analog
input configuration switches properly.

Product Description

10

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL