Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 66

Advertising
background image

Next use the down arrow to proceed to the next section.
If this is the first time the Genie has run, the Genie will guide the user through the setup of
the motor parameters. If the Genie has run previously, the user can choose the desired
Setup Selection to configure a specific function in the controller. Use the up and down
arrows to highlight the desired setup and press [OK] to enter the setup. The choices for
the Setup Selection menu are described in the table below.

Table 17: Setups with the Genie

Setup

Description

Motor

This setup allows configuration of the motor parameters.

These settings are found on the motor nameplate.

Application

The Application setup allows the user to configure the

motor type, operating mode, units and ramps.

Feedback

This setup allows configuration of up to 3 feedback

sources. The feedbacks can be taken in to the controller

through analog inputs or communications.

Setpoint

This setup allows configuration of up to 2 setpoints. If

multiple setpoints are used, the setpoint is selected by

using DI 33.

Constant Slave

This setup configures the controller to operate up to 2

external fixed speed pumps using the 2 on board relays.

Flow Compensation

This setup configures the Flow Compensation function

which can automatically adjust the system setpoint to

offset the affect of friction loss in the system.

Pump Protection

This setup configures Sleep Mode, Flow Check, No Water/

Loss of Prime and Pump Protect functions.

Digital Input

This setup allows configuration of the digital inputs.

Relay and Analog Output

This setup allows configuration of the relay and analog

outputs.

Communication

This setup configures the on board fieldbus

communications.

Copy to LCP

This setup allows all the controller parameters to be

copied to the LCP. This is helpful for saving the drive state

or to quickly configure another controller with the same

settings.

Copy from LCP

This setup allows all the controller parameters to be

copied from the LCP. This is helpful for reverting the drive

to a previous state or to quickly configure another

controller with the same settings.

Motor setup

The motor data required to complete the Motor Setup can be found on the motor
nameplate. The Start-Up Genie will prompt the user for Motor Power (HP), Motor Nominal
Voltage, Motor Nominal Frequency (Hz), Motor Nominal Speed (RPM), Motor Current
(FLA), Motor Service Factor (%) and Motor Type. If the Motor Service Factor indicated on
the motor nameplate is 1.15 enter 115% for Motor Service Factor. Be sure to properly set

Operation

64

Aquavar

®